Cummins 300DQHAB 270kW Prime Rated Mobile Diesel Generator on Gooseneck Trailer with 500 Gallon Fuel Tank
Cummins Power Generation
Commercial
generator sets are fully integrated power generation systems providing optimum
performance, reliability and versatility for stationary standby and prime power
applications.
Features
Cummins® heavy-duty engine - Rugged 4-cycle, industrial
diesel delivers reliable power, low emissions and fast response to load
changes.
Control system The PowerCommand® electronic control is standard equipment and provides total
genset system integration including automatic remote starting/stopping, precise
frequency and voltage regulation, alarm and status message display, AmpSentry™
protection, output metering, auto-shutdown at fault detection and NFPA 110
Level 1 compliance.
Cooling system Standard cooling package provides reliable running, at the rated power level,
at up to 52 °C (126 °F) ambient temperature.
Warranty Full factory Warranty
See more Cummins Power Generations Diesel Generators!
Diesel Genset: 60Hz-270kW |
|
Install-US-Nonroad |
U.S. EPA, Nonroad (Portable) Application |
300DQHAB |
Genset-Diesel,60Hz,270kW |
A122-2 |
Duty Rating-Prime Power |
L090-2 |
Listing-UL 2200 |
L171-2 |
Emissions-Compliance,TPEM,EPA OEM Transition Program |
L227-2 |
Non-Cummins TPEM Allowance TPEM OWNER 77415 |
F183-2 |
Enclosure-Steel,Weather Prot,w/ExhSys,Res Muffler |
R002-2 |
Voltage-277/480,3 Phase,Wye,4 Wire |
B258-2 |
Alternator-60 Hz, 12 Lead, Extended Range,125/105C |
H643-2 |
SET CONTROL-PCC 2100 |
H536-2 |
Display Language-English |
H605-2 |
Display-Control,Graphical |
H606-2 |
Meters-AC Output,Analog |
K631-2 |
Relays-Genset Status, User Configured |
KU93-2 |
CB or EB or TB-Left Only |
KU09-2 |
CirBrkr-400A,Left,3P,600/690V,SS RMS,80%,UL/IEC |
KB73-2 |
CB or EB or TB-Bottom Entry, Left |
C127-2 |
Separator-Fuel/Water |
E125-2 |
Engine Cooling-High Ambient Air Temperature |
H389-2 |
Shutdown-Low Coolant Level |
H557-2 |
Coolant Heater-208/240/480V, Below 40F Ambient Temp. Wired to receptacle external to enclosure. |
D041-2 |
Engine Air Cleaner-Normal Duty |
CCV |
Crankcase Vapor recovery system, RACOR |
L028-2 |
Genset warranty- Base, Standby 2 years / 400 hours, Prime Power 1 year / unlimited hours, Continuous Power 1 year / unlimited hours |
L050-2 |
Literature-English |
TRAILER |
Gooseneck/ 5th wheel Trailer, 8K pound axles. Per owner Specifications with steel floor. Includes front mounted dual wall fuel tank, 500 Gallon capacity **NOT FOR TRANSPORT FULL** |
Z777-2 |
TPEM Approval Required – TPEM OWNER 77415 |
CAMCONNECT |
Cam-Lok Connection system, E1016 female connectors. 1 for each phase and neutral /ground. With protective covers. Installed external to enclosure. |
BATTSYS |
Install Battery System. Includes Battery disconnect system, Starting Battery and Battery Maintainer. Battery Charger wired to receptacle external to enclosure. |
Link to Spec Sheet PDF: Liquid-Diesel-300kw-Spec-Sheet