Echo DGK70F Diesel Generator

https://www.bmr.energy/web/image/product.template/4955/image_1920?unique=e3867a0

Echo DGK70F 70 kVA industrial diesel generator — 56 kW (70 kVA) 3-phase / 42 kW 1-phase continuous, 61 dB(A) at 23 ft, Isuzu 4JJ1X, 4 cylinder, 24 hr runtime at full load.

The ECHO DGK70F is a Tier 4 Final mobile diesel generator rated 56 kW (70 kVA) continuous three-phase and 42 kW continuous single-phase, built around an Isuzu 4JJ1X 4-cylinder engine in an enclosure ECHO rates at 61 dB(A) at no load, measured at 23 ft. It is designed for rental fleets and contractors — equipment that gets used hard, moved often, and maintained on a schedule.

Altitude

ECHO does not publish a derate figure for this machine — not on the sell sheet and not on the spec page. That is worth saying plainly rather than filling the gap with someone else's number. What the sheet does give is the engine and how it breathes, and here that works in your favour: this one is direct injection, turbocharged, intercooled, with DOC and SCR. A turbocharged diesel holds its rating at elevation far better than a naturally aspirated one, because the turbo restores intake density that thin air takes away. On the Front Range that difference is worth real money — it is often the reason a turbocharged set one size down does the job that a naturally aspirated set one size up cannot.

We are at 6,035 ft in Colorado Springs and we sell into sites well above that. Tell us the elevation the machine will actually work at and we will get the derate in writing from ECHO before you order, rather than after you find out. A set that is quietly short of its nameplate at 8,000 ft is the most common and most expensive mistake in this business, and it is entirely avoidable.

Options. Trailer, block heater, battery charger, cam locks, fire extinguisher and shore power are factory options ordered with the unit — ask and we will quote the machine as you actually want it configured.

56,461.00 56461.0 USD 56,461.00

56,461.00

Not Available For Sale

This combination does not exist.

Terms and Conditions
30-day money-back guarantee
Shipping: 2-3 Business Days

Specifications

Continuous output56 kW (70 kVA) 3-phase / 42 kW 1-phase
Standby output61.6 kW (77 kVA) 3-phase
Voltage240 / 480V 3-phase, 120 / 139 / 240 / 277V 1-phase
Amperage175A x 2 @ 120V, 168A @ 240V 3-phase, 84A @ 480V
Sound level (no load, 23 ft)61 dB(A)
Sound level (full load, 23 ft)62 dB(A)
EngineIsuzu 4JJ1X, 4 cylinder
Engine designDirect injection, turbocharged, intercooler, DOC and SCR
Displacement183.0 cu. in. (2.999 L)
Rated output95.2 hp (71.0 kW) @ 1800 rpm
Rated speed1800 rpm
Starting systemElectric 12V DC
EmissionsUS EPA Tier 4 Final
Fuel capacity105.0 gal
Fuel consumption (full load)4.4 gal/hr
Fuel consumption (1/2 load)2.5 gal/hr
Runtime at full load~24 hours
DEF capacity7.4 gal
Dimensions (L x W x H)102" x 37.5" x 69"
Dry weight3,898 lbs
Trailered dimensions156.06" x 68.0" x 84.95"
Trailered dry weight4,998 lbs

Features and specifications

  • Isuzu 4JJ1X diesel. Direct injection, turbocharged, intercooled, with DOC and SCR, 183.0 cu in (2.999 L), 95.2 hp (71.0 kW) @ 1800 rpm. US EPA Tier 4 Final.
  • Standby rating. 61.6 kW (77 kVA) three-phase, above the continuous rating, for backup duty rather than prime power.
  • Output. 240 / 480 V three-phase and 120 / 139 / 240 V (277 V) single-phase. 175 A x2 at 120 V and 175 A at 240 V single-phase; 168 A at 240 V and 84 A at 480 V three-phase. Frequency regulation 60 Hz ±0.25%.
  • Simul-Phase®. Single-phase and three-phase output at the same time, from the same machine, without a transformer. One set covers a mixed site instead of two.
  • Priority trip breakers. Separate breakers for single- and three-phase loads, so an overload on one side does not take down the other.
  • S.E.T. Smart Emissions Technology™. Protects the aftertreatment during light or underloaded running — which is most of what a rental set actually does.
  • Fuel. 105 gal (400 L) internal with 110% fluid containment. Burn is 4.4 gal/hr at full load, 3.4 at 3/4, 2.5 at 1/2 and 1.8 at 1/4 — about 24 hours at full load on the internal tank, less as you load it harder than a rental set usually runs.
  • DEF. 7.4 gal (28.0 L).
  • Sound. 61 dB(A) at no load and 62 dB(A) at full load at 23 ft, using a tuned muffler, longer exhaust and air dams that double the cooling path rather than insulation alone.
  • Size and weight. 102" x 37.5" x 69", 3,898 lb dry. Trailered: 156.06" x 68.0" x 84.95", 4,998 lb.
  • Alternator. Revolving field brushless AC. 12 V DC electric starting.

Ultra-quiet design

Echo industrial generators are built for sound-sensitive jobsites: air dams and insulated panels double the cooling air path, heavy-gauge door panels and sound-absorbing foam damp the enclosure, and a tuned muffler with an extended exhaust pipe cuts both high and low frequency noise -- without power-robbing auxiliary fans.

Simul-Phase®

Simul-Phase® delivers single- and three-phase power at the same time from a split buss, with 120/240V single-phase available at every voltage setting -- no transformer required. Priority trip breakers separate single- and three-phase loads so preferred circuits stay up during an overload.

S.E.T. Smart Emissions Technology™

S.E.T. Smart Emissions Technology™ provides added aftertreatment protection during light or underloaded operation -- the condition that most often fouls Tier 4 emissions systems on standby and rental duty.

Available accessories

Sold and serviced by Blue Mountain Reserve — serving Colorado, Wyoming and New Mexico. Contact us for lead times, freight quotes, dealer pricing and startup support.