Cummins C50D6C 50 kW Diesel Standby Generator Package with 200 A SE-Rated ATS (Minturn Station 5)
Cummins C50D6C diesel standby generator set, 50 kW, 60 Hz
Rated 200 A at 7,900 ft elevation; standby power (ESP) duty rating
120/240 V, single phase, 3 wire; alternator 60 Hz, reconnectable, full output, 105C, IMS
Permanent magnet exciter/regulator; electronic isochronous governor; 12 V DC starter
UL 2200 listed; NFPA 110 Type 10 Level 1 capable; EPA stationary emergency, Tier 3 (NSPS CI)
Aluminum Level 2 sound attenuated enclosure with exhaust system, sandstone color
Enclosure wind load 180 MPH (ASCE 7-10); enclosure installation kit; intake baffle (shipped loose)
Skidbase, housing ready; UL 142 dual-wall sub-base diesel fuel tank, 24-hour minimum
Fuel water separator; 40% low fuel level switch; mechanical fuel gauge; fuel tank rupture basin switch
PowerCommand 2.3 controller, left-facing mounting; oil pressure gauge; AC output meters
Emergency stop switch; 8-input / 8-output auxiliary signals; English display
Load connection single; circuit breaker, location A, 70-250 A, 3P, LSI, 600 V AC
Engine: high ambient radiator; 50/50 coolant; extreme cold coolant heater; 120 V oil heater; battery heater kit
Shutdown on low coolant level; normal duty air cleaner; battery charging alternator
Batteries: (2) Group 35; 6 A regulated battery charger
System start-up and testing included
2-year genset warranty
Delivery to site; off-loading and initial fuel fill are separate lines
Transfer switch: 200 A service-entrance-rated automatic transfer switch, NEMA 3R
PowerCommand transfer switch, electronic control (PC40), 3-pole solid neutral
UL 1008 / CSA listed; 240 V AC, 60 Hz, single phase, 2 or 3 wire
Integral control power supply; load phase power monitoring
Genset starting battery 12 V DC
Auxiliary relays: emergency and normal position (12 V DC); auxiliary contact module (8)
MODBUS RTU communications module; elevator signal relay
Control panel security key cover
2-year comprehensive transfer switch warranty